Electrical · Free · Instant results

kW to kVA & kVA to kW Calculator

Calculate Smarter. Work Faster.

Convert kW to kVA or kVA to kW instantly using power factor. Enter the value and PF — used for generator, transformer and UPS sizing.

Power Conversion Details

Choose the conversion direction and enter your known value and power factor.

Conversion Direction
kW = kVA × PF kVA = kW ÷ PF
Real Power
— kW

Converted using your power factor

Formula Used
Enter values and hit calculate to see the worked formula.
Did this solve your problem?

Created by Umasankar Maity — B.Tech in Electrical Engineering, with 11+ years of industrial maintenance experience.

Reviewed by the ElectroMechCalc editorial team.

Last reviewed: September 2026  |  Standards referenced: IEC / IEEE / BIS / NEC

How it works

Power Triangle: kW, kVA, kVAR & Power Factor

Quick answer: kW = kVA × PF and kVA = kW ÷ PF. Example: 125 kVA × 0.8 = 100 kW; 100 kW ÷ 0.8 = 125 kVA.

φ kW = 100 (Real Power, P) kVAR = 75 (Reactive, Q) kVA = 125 (Apparent Power, S) PF = cos φ = 0.8 FORMULAS kW = kVA × PF kVA = kW ÷ PF PF = kW ÷ kVA kVA² = kW² + kVAR² kVAR = √(kVA²−kW²) kVAR = kVA × sin φ PF = cos φ Example: 125 kVA @ 0.8 PF → 100 kW, 75 kVAR
Power triangle: kW (base) and kVAR (height) combine at 90° to give kVA (hypotenuse). The angle φ between kW and kVA sets the power factor.
  • kW (real power, P): the base of the triangle — power that does useful work.
  • kVAR (reactive power, Q): the vertical side — drawn by motors, transformers and ballasts; does no useful work.
  • kVA (apparent power, S): the hypotenuse — total power the supply must deliver: kVA = √(kW² + kVAR²).
  • Power factor (PF = cos φ): kW ÷ kVA, between 0 and 1. Closer to 1 = less reactive power, smaller kVA for the same kW.
kVA = √(kW² + kVAR²) kVAR = √(kVA² − kW²) PF = cos φ = kW ÷ kVA
QuantitySymbolUnitWhat it means
Real (active) powerPkWPower doing useful work — heat, light, motion
Reactive powerQkVARPower for magnetic fields of motors and transformers — no useful work
Apparent powerSkVATotal power the supply, cable and generator must carry
Power factorPF = cos φ—Share of kVA that becomes kW (0 to 1)
Formulas

kW to kVA & kVA to kW Formula

kVA to kW Conversion

kW = kVA × PF
  • Example: 80 kVA × 0.8 = 64 kW.
  • Example: 8 kVA × 0.8 = 6.4 kW.

kW to kVA Conversion

kVA = kW ÷ PF
  • Example: 22 kW ÷ 0.8 = 27.5 kVA.
  • Example: 40 kW ÷ 0.8 = 50 kVA.

How to Use the Calculator

  1. Choose direction: kVA to kW or kW to kVA.
  2. Enter the known value (kVA or kW).
  3. Enter power factor — nameplate or measured value; 0.8 if unknown.
  4. Click Calculate to see the result and the worked formula.

kW to kVA at Different Power Factors

Same 100 kW load — lower PF needs more kVA capacity:

Power FactorEquivalent kVA for 100 kW Load
1.00 (unity)100.0 kVA
0.95105.3 kVA
0.90111.1 kVA
0.80125.0 kVA
0.70142.9 kVA
0.60166.7 kVA

Common Power Factor Values by Load Type

Use a realistic PF for your load instead of a blanket 0.8:

Load TypeTypical PF (uncorrected)
Incandescent/resistive heating0.95 – 1.0
LED lighting (with driver)0.9 – 0.95
Induction motors (loaded)0.8 – 0.88
Induction motors (lightly loaded)0.5 – 0.7
Welding equipment0.4 – 0.6
Diesel generator (typical rating basis)0.8
1-phase & 3-phase

kVA to kW for Single-Phase and Three-Phase

  • kW ↔ kVA is the same for both: kW = kVA × PF. Phase does not change this ratio.
  • Phase matters only from voltage and current:
1-phase: kVA = V × I ÷ 1000 1-phase: kW = V × I × PF ÷ 1000 3-phase: kVA = √3 × VLL × I ÷ 1000 3-phase: kW = √3 × VLL × I × PF ÷ 1000
Quick reference

kW to kVA & kVA to kW Conversion Tables

kW to kVA Quick Reference Table (1-100 kW)

At 0.8 PF (kVA = kW ÷ 0.8).

kWkVA (at 0.8 PF)
1 kW1.25 kVA
2 kW2.50 kVA
3 kW3.75 kVA
4 kW5.00 kVA
5 kW6.25 kVA
6 kW7.50 kVA
7 kW8.75 kVA
8 kW10.00 kVA
9 kW11.25 kVA
10 kW12.50 kVA
11 kW13.75 kVA
12 kW15.00 kVA
13 kW16.25 kVA
14 kW17.50 kVA
15 kW18.75 kVA
16 kW20.00 kVA
17 kW21.25 kVA
18 kW22.50 kVA
19 kW23.75 kVA
20 kW25.00 kVA
21 kW26.25 kVA
22 kW27.50 kVA
23 kW28.75 kVA
24 kW30.00 kVA
25 kW31.25 kVA
26 kW32.50 kVA
27 kW33.75 kVA
28 kW35.00 kVA
29 kW36.25 kVA
30 kW37.50 kVA
31 kW38.75 kVA
32 kW40.00 kVA
33 kW41.25 kVA
34 kW42.50 kVA
35 kW43.75 kVA
36 kW45.00 kVA
37 kW46.25 kVA
38 kW47.50 kVA
39 kW48.75 kVA
40 kW50.00 kVA
41 kW51.25 kVA
42 kW52.50 kVA
43 kW53.75 kVA
44 kW55.00 kVA
45 kW56.25 kVA
46 kW57.50 kVA
47 kW58.75 kVA
48 kW60.00 kVA
49 kW61.25 kVA
50 kW62.50 kVA
51 kW63.75 kVA
52 kW65.00 kVA
53 kW66.25 kVA
54 kW67.50 kVA
55 kW68.75 kVA
56 kW70.00 kVA
57 kW71.25 kVA
58 kW72.50 kVA
59 kW73.75 kVA
60 kW75.00 kVA
61 kW76.25 kVA
62 kW77.50 kVA
63 kW78.75 kVA
64 kW80.00 kVA
65 kW81.25 kVA
66 kW82.50 kVA
67 kW83.75 kVA
68 kW85.00 kVA
69 kW86.25 kVA
70 kW87.50 kVA
71 kW88.75 kVA
72 kW90.00 kVA
73 kW91.25 kVA
74 kW92.50 kVA
75 kW93.75 kVA
76 kW95.00 kVA
77 kW96.25 kVA
78 kW97.50 kVA
79 kW98.75 kVA
80 kW100.00 kVA
81 kW101.25 kVA
82 kW102.50 kVA
83 kW103.75 kVA
84 kW105.00 kVA
85 kW106.25 kVA
86 kW107.50 kVA
87 kW108.75 kVA
88 kW110.00 kVA
89 kW111.25 kVA
90 kW112.50 kVA
91 kW113.75 kVA
92 kW115.00 kVA
93 kW116.25 kVA
94 kW117.50 kVA
95 kW118.75 kVA
96 kW120.00 kVA
97 kW121.25 kVA
98 kW122.50 kVA
99 kW123.75 kVA
100 kW125.00 kVA

kVA to kW Quick Reference Table (1-100 kVA)

At 0.8 PF (kW = kVA × 0.8) — read a generator or UPS kVA rating straight across to kW.

kVAkW (at 0.8 PF)
1 kVA0.80 kW
2 kVA1.60 kW
3 kVA2.40 kW
4 kVA3.20 kW
5 kVA4.00 kW
6 kVA4.80 kW
7 kVA5.60 kW
8 kVA6.40 kW
9 kVA7.20 kW
10 kVA8.00 kW
11 kVA8.80 kW
12 kVA9.60 kW
13 kVA10.40 kW
14 kVA11.20 kW
15 kVA12.00 kW
16 kVA12.80 kW
17 kVA13.60 kW
18 kVA14.40 kW
19 kVA15.20 kW
20 kVA16.00 kW
21 kVA16.80 kW
22 kVA17.60 kW
23 kVA18.40 kW
24 kVA19.20 kW
25 kVA20.00 kW
26 kVA20.80 kW
27 kVA21.60 kW
28 kVA22.40 kW
29 kVA23.20 kW
30 kVA24.00 kW
31 kVA24.80 kW
32 kVA25.60 kW
33 kVA26.40 kW
34 kVA27.20 kW
35 kVA28.00 kW
36 kVA28.80 kW
37 kVA29.60 kW
38 kVA30.40 kW
39 kVA31.20 kW
40 kVA32.00 kW
41 kVA32.80 kW
42 kVA33.60 kW
43 kVA34.40 kW
44 kVA35.20 kW
45 kVA36.00 kW
46 kVA36.80 kW
47 kVA37.60 kW
48 kVA38.40 kW
49 kVA39.20 kW
50 kVA40.00 kW
51 kVA40.80 kW
52 kVA41.60 kW
53 kVA42.40 kW
54 kVA43.20 kW
55 kVA44.00 kW
56 kVA44.80 kW
57 kVA45.60 kW
58 kVA46.40 kW
59 kVA47.20 kW
60 kVA48.00 kW
61 kVA48.80 kW
62 kVA49.60 kW
63 kVA50.40 kW
64 kVA51.20 kW
65 kVA52.00 kW
66 kVA52.80 kW
67 kVA53.60 kW
68 kVA54.40 kW
69 kVA55.20 kW
70 kVA56.00 kW
71 kVA56.80 kW
72 kVA57.60 kW
73 kVA58.40 kW
74 kVA59.20 kW
75 kVA60.00 kW
76 kVA60.80 kW
77 kVA61.60 kW
78 kVA62.40 kW
79 kVA63.20 kW
80 kVA64.00 kW
81 kVA64.80 kW
82 kVA65.60 kW
83 kVA66.40 kW
84 kVA67.20 kW
85 kVA68.00 kW
86 kVA68.80 kW
87 kVA69.60 kW
88 kVA70.40 kW
89 kVA71.20 kW
90 kVA72.00 kW
91 kVA72.80 kW
92 kVA73.60 kW
93 kVA74.40 kW
94 kVA75.20 kW
95 kVA76.00 kW
96 kVA76.80 kW
97 kVA77.60 kW
98 kVA78.40 kW
99 kVA79.20 kW
100 kVA80.00 kW
Generators & transformers

Generator & Transformer kVA to kW

  • Generators (DG sets) are rated in kVA; usable kW is normally quoted at 0.8 PF.
  • Transformers and UPS are rated in kVA because heating depends on current, not PF.
  • Never treat a kVA rating as kW — a 125 kVA DG gives about 100 kW, not 125 kW.
Generator kW = kVA × 0.8 Required kVA = Load kW ÷ Load PF

Common kVA Ratings in kW

kVA RatingkW at 0.8 PFkW at 0.9 PF
125 kVA100 kW112.5 kW
150 kVA120 kW135 kW
200 kVA160 kW180 kW
250 kVA200 kW225 kW
300 kVA240 kW270 kW
450 kVA360 kW405 kW
500 kVA400 kW450 kW
630 kVA504 kW567 kW
1000 kVA800 kW900 kW
1500 kVA1200 kW1350 kW
2000 kVA1600 kW1800 kW

Generator Sizing Example

  1. Load: 80 kW mixed load at PF 0.85.
  2. kVA = 80 ÷ 0.85 ≈ 94.1 kVA.
  3. Add margin for motor starting and future load; round up to a standard size.
  4. Practical choice: 125 kVA DG (100 kW at 0.8 PF). Check with the DG size calculator.

Transformer Sizing Example

  1. Load: 315 kW at PF 0.9 → kVA = 315 ÷ 0.9 = 350 kVA.
  2. Same load at PF 0.75 → kVA = 315 ÷ 0.75 = 420 kVA — a full size class higher.
  3. Lesson: correcting PF with an APFC capacitor bank is often cheaper than a bigger transformer. See the transformer size calculator.

Industrial Applications

  • UPS / data centre: kVA = IT load kW ÷ PF (often 0.9–0.95).
  • Utility billing: kVA demand charges drop when PF improves.
  • Standby / prime DG selection: convert site kW to kVA at the real PF.
  • Panel capacity: check kVA (not just kW) headroom before adding loads.

Reference: kW/kVA/PF relationships are standard IEC/IEEE electrical engineering conventions used across generator, transformer, and UPS sizing worldwide. This calculator is for preliminary, educational sizing only.

Common Mistakes

Mistakes to Avoid in kVA/kW Conversion

  1. Using 0.8 PF for everything. Real PF ranges from ~0.5 (lightly loaded motors) to ~1.0 (resistive/LED) — use measured or nameplate PF.
  2. Sizing to the bare calculated kVA. Round up for motor inrush, load growth and PF drift.
  3. Reading kVA as kW. 125 kVA ≠ 125 kW unless PF = 1.0.
  4. Buying a bigger transformer instead of correcting PF. APFC is usually cheaper.
  5. Not rechecking kVA after adding loads. Recalculate total kVA demand, not just kW.
FAQ

kW to kVA & kVA to kW — FAQs

How do I convert kVA to kW? +

Multiply kVA by the power factor: kW = kVA × PF. For example, 125 kVA × 0.8 = 100 kW.

How do I convert kW to kVA? +

Divide kW by the power factor: kVA = kW ÷ PF. For example, 100 kW ÷ 0.8 = 125 kVA.

How many kVA is 1 kW? +

At 0.8 power factor, 1 kW = 1.25 kVA. At unity power factor (1.0), 1 kW = 1 kVA.

What is 125 kVA in kW? +

125 kVA = 100 kW at 0.8 PF, or 112.5 kW at 0.9 PF.

What is the kVA to kW formula for 3 phase? +

The conversion is the same for single and three phase: kW = kVA × PF. Phase only matters when you start from voltage and current: 3-phase kVA = √3 × V × I ÷ 1000; single-phase kVA = V × I ÷ 1000.

What is the difference between kVA and kW? +

kVA is apparent power — the total power supplied. kW is real power — the part that does useful work. The difference is reactive power (kVAR), needed by motors and transformers but doing no useful work.

What power factor should I use if I don't know it? +

0.8 lagging is the common default for mixed industrial loads and diesel generators. Check the nameplate first: heaters are near 1.0, lightly loaded motors can drop to 0.5–0.7.

Why are generators rated in kVA instead of kW? +

The alternator is limited by current, so its basic rating is kVA. Usable kW depends on load PF — manufacturers usually quote kW at 0.8 PF, so a 125 kVA generator gives about 100 kW.

Can power factor correction reduce my kVA requirement? +

Yes. APFC capacitor banks raise PF towards 1, lowering kVA for the same kW. This frees transformer and cable capacity and can cut kVA-demand charges and low-PF penalties.

What PF should I use for a mixed load? +

Use the combined PF measured at the main incoming panel (power meter or utility bill) instead of averaging individual equipment PF values.

Is kVA the same as kWh? +

No. kVA is apparent power at an instant; kWh is energy used over time. Formula: kWh = kW × hours = kVA × PF × hours. Example: a 10 kVA load at 0.8 PF running 5 hours uses 10 × 0.8 × 5 = 40 kWh. The formula assumes a constant load — for varying loads, use a kWh meter reading.

Explore More Categories